YXC8VZ3V-R / N2XSEYFGbY (3.6/6kV, 6/10 kV, 8.7/15 kV, 12/20 kV, 18/30 kV, 20.3/35 kV)
-
YXC8V-R / N2XSEY 20.3/35 kV
-
YXC8VZ4V-R / N2XSEYBY 20.3/35 kV
-
YXC8VZ3V-R / N2XSEYFGbY 20.3/35 kV
-
YXC8VZ2V-R / N2XSEYRGbY 20.3/35 kV
-
YAXC8VZ3V-R / NA2XSEYFGbY 20.3/35 kV
Structure
- Multi-stranded aluminum conductor
- Inner semi-conductive layer
- XLPE insulation
- Outer semi-conductive layer
- Semi-conductive tape
- Copper screen
- Filler
- Inner sheath
- Flat galvanized steel armor
- Galvanized steel tape
- PVC outer sheath
Technical Specifications
Maximum operating temperature: 90°C
Maximum short-circuit temperature: 250°C (+ ≤ 5 seconds)
Minimum laying temperature: -5°C
Standard: TS IEC 60502-2 VDE 0276
Usage Area
These cables are used in electrical power supply for residential and industrial areas where short-circuit currents are high, outdoors, in cable trays, indoors, and underground. Additionally, these cables are used in places with mechanical stresses.